Ready · client-side
⚡ POWER EDITION — FEEDERS · TRANSFORMERS · FAULT LEVELS · NETWORK ANALYSIS

Design. Check. Energize.

Feeder voltage drop, transformer sizing, cable sizing, fault levels, network analysis, single-line diagrams and professional reports — all running instantly in your browser. No server, no uploads.

10power modules
6report tables
100%client-side
👋 New here? Each section has a “How this works” panel with a plain-English explanation and a one-click worked example.
01

Power Systems

Per-unit base, feeder voltage drop, transformer sizing, LV cable sizing and transformer-bus fault level — ported from PowerSys Pro + psextract.

◈System Base

Per-unit reference shared by fault calculations below.

〜Feeder Voltage Drop

3-phase feeder drop from R/X per km, length, load and PF.

▣Transformer Sizing + Fault Level

Recommended standard size, utilisation and symmetrical/asymmetrical fault current.

🔌LV Cable Sizing IEC 60364

Copper XLPE, derated for installation + ambient, with VD check.

⚠Short-Circuit at Bus

Fault current at transformer LV bus including feeder impedance.

📏Design Standards

Switches formulas, limits and references across the calculators.

📈Live Load Study 0–150%

Drag the slider — feeder VD, transformer loading and cable VD recalculate live from your inputs above. Same slider drives SLD loading colours.

100%
02

Power Flow (Load Flow)

Newton–Raphson AC load flow on a user-editable network. Edit bus loads/generation and branch impedances, then solve — bus voltages, angles, branch flows and losses are computed, not mocked. Bus type: slack (1, reference), PV (generator, holds V), PQ (load).

Buses — edit V (kV), Type, P (kW), Q (kVar); Vm/angle are solved

#NameV kVTypeP kWQ kVarVm p.u.Va °

Branches — R, X in Ω, rating kVA

FromToR ΩX ΩRate kVAP→ kWQ→ kVarLoad %Loss kW
Ready — press Solve load flow.
03

Motor Starting — Voltage Dip

Locked-rotor inrush and the voltage dip it imposes at the point of common coupling (PCC). Impedance-divider method per IEC 60034-12 / AS-NZS 3000 §3.5. Checks against typical start-dip limits.

ⓂMotor + Supply

Motor nameplate + upstream fault level at the PCC.

📉Start Method Comparison

Same motor started four ways — effective inrush and resulting PCC dip.

MethodI_start ADip %Status
04

Cable Short-Circuit Withstand

Adiabatic thermal check (IEC 60364-4-43 / BS 7671): a conductor must survive fault energy I²t without exceeding its insulation temperature. Computes minimum area and maximum permissible clearing time.

🔥Adiabatic Check k²S² ≥ I²t

k from material + insulation (BS 7671 Table 43.1).

📋k Factors

Typical conductor k (BS 7671 Table 43.1), for ≤5 s faults.

InsulationCuAl
XLPE / EPR (90°C)14394
PVC (70°C)11576
PVC (90°C)10066
Bare conductor176116
05

Power Factor Correction

Size a capacitor bank to raise power factor to a target: Q_c = P·(tan φ₁ − tan φ₂). Includes detuning note for harmonic-rich systems.

⚙Capacitor Sizing

Existing load + present/target power factor.

📊What changes

Before vs after correction.

QuantityBeforeAfter
06

Arc Flash Hazard IEEE 1584-2018

Incident energy and arc-flash boundary per the IEEE 1584-2018 empirical model (1,800+ tests): arcing current (with reduced-current case), enclosure size correction, and PPE category per NFPA 70E. Safety-critical — verify against your protection study before use.

⚡Arc Flash Calculation

Equipment + fault data. Voltage 208 V–15 kV; G per equipment class.

🦺PPE Category NFPA 70E

PPE category from the highest (reduced-current) incident energy.

CaseI_arc kAE cal/cm²AFB mmPPE
PPE CatIncident energy
0 / none≤ 1.2 cal/cm²
1≤ 4
2≤ 8
3≤ 25
4≤ 40
07

Network Analysis Report

psextract-style system report. Edit bus voltages live — compliance re-evaluates instantly. Sample 5-bus demo case preloaded.

Bus Results — click Vm / load cells to edit

BusNameV (kV)Vm (p.u.)Va (°)P (kW)Q (kVar)Status

Branch Power Flows

FromToPf (kW)Qf (kVar)Loading %Status

Short-Circuit Analysis (Z-bus method, sample)

BusI_sc (kA)S_sc (MVA)Z_sc (Ω)Breaker ≥

NERC Compliance

CheckResultStatus

Generator Dispatch

UnitP (kW)Q (kVar)Vset (p.u.)Profile
08

Single-Line Diagram Builder

Click a component on the left to drop it on the canvas — there are no modes to learn. The new symbol is placed for you and, if something is already selected, wired to it automatically, so you can build a feeder by simply clicking Generator → Breaker → Busbar → Transformer → Motor. To connect two things by hand, drag a ● dot onto another symbol — it snaps for you, so you don't need to aim precisely. The canvas is unlimited: pan with Space-drag or middle-drag and zoom out freely, and the grid follows you. Drag a symbol to move it (it snaps to the grid and shows alignment guides against its neighbours), click a breaker to open or close it, double-click a load to change its loading.

Components

Click to add · or drag onto the canvas

Start from a template

Start over

🗺 Draw your single-line diagram

Click a component on the left to drop it here — or start from a ready-made template.

Click a component to add · drag a ● dot to connect (it snaps) · wheel = zoom · ✋ Pan / Space / middle / right-drag = move the plane · arrows = nudge · Del = delete
0 components · 0 connections

Properties

Select an element to edit its properties.
09

Engineering Report

Collects your latest results from every module above into one professional report. Print or save as PDF.